IO619 Usage Notes
IO619 Usage Notes — Usage information about the
I/O module
General
To use the I/O module as a bus administrator, a configuration file containing the
timing information of each port is required. A second configuration file can be used
to automatically configure the Process Data block depending on the selected
device.
The file types supported are: .csv and .xls. The configuration file must contain a
header row, followed by the data values. Refer to the files below to see how the
headers must look and which data is required.
Bus Administrator Configuration File
To properly configure an I/O module as a bus administrator, a configuration file
with the following data is required:
PortAddress must be a hexadecimal value. PortSize must be specified in bytes and
must not exceed 32. PortCycleTime must be a multiple of 1 ms, and must not
exceed 1024 ms. Slot can be a value between 0 and 1023.
Device Configuration File
To automatically configure the process data block, a configuration file with the
following data is required:
For each device, at least one port and one variable must be specified. To make the
configuration file more readable, cells used only to fill gaps can be left empty. A
new device/port is detected as soon as the value of DeviceName/PortName changes or is no longer empty.
The DeviceAddress and PortAddress must be hexadecimal values. PortDirection can
either be "Source" or "Sink". PortCycleTime must be a multiple of 1 ms, and
must not exceed 1024 ms. PortSize must be specified in bytes and must not
exceed 32. VariableOffset and VariableSize must be values in bits.