Modbus - Client Transceiver

Modbus - Client Transceiver — Reads/writes data from/to the input/output port of the block

Library

Simulink Real-Time - Speedgoat

Description

This block is used to exchange data with the remote Modbus TCP Server. Your model can contain multiple Modbus TCP Client Transceiver blocks for each Modbus Connection in your target machine.

Ports

Inputs
Tx

Array of length Quantity that includes the values to be sent to the Modbus Server for the data range specified by the Index and Quantity parameters. The data type depends on the selected function code.

  • For Coils and Discrete Inputs, the input port is a vector of the BOOLEAN data type where the length of the vector is defined by the Quantity parameter. Each BOOLEAN element of the vector represents one bit.

  • For Holding Registers and Input Registers, the input port is a vector of the UINT16 data type where the length of the vector is defined by the Quantity parameter. Each UINT16 element of the vector represents one word/register.

Use Byte Pack blocks to convert signed values or floating-point numbers. You can pack one double value to a vector of type uint16 and length 4.

ENA

Boolean input to allow the user to manage the handling of Modbus requests to the defined Modbus Server. This input is only active if the Manage Requests checkbox is enabled. Send a boolean value of 1 to enable sending or 0 to disable the sending of Modbus requests. If the sending is stopped, the Transceiver will still be able to receive data and update its output port.

Outputs
Rx

Array of length Quantity that includes the values received from the Modbus Server for the data range specified by the Index and Quantity parameters. The data type depends on the selected function code.

  • For Coils and Discrete Inputs, the output port is a vector of the BOOLEAN data type where the length of the vector is defined by the Quantity parameter. Each BOOLEAN element of the vector represents one bit.

  • For Holding Registers and Input Registers, the output port is a vector of the UINT16 data type where the length of the vector is defined by the Quantity parameter. Each UINT16 element of the vector represents one word/register.

Use Byte Unpack blocks to convert to signed values or floating-point numbers. You can unpack a vector of type uint16 and length 4 to one double value.

Parameters

Client Station ID

Apply the Client Station ID of the corresponding Setup block. Must range between 0 and 65535.

Connection ID

Apply the Connection ID of the corresponding Connection block. Must range between 0 and 65535.

Remote Server Unit ID

Typical Modbus Servers that do not act as a Modbus RTU gateway have only one unit. If the Modbus Server is accessed through a bridge or gateway, then it can contain multiple units. The Unit ID is necessary to identify the units. Check the official Implementation Guide for more information about this topic.

Apply the Unit ID to address the remote Unit in the Modbus TCP Server. You can assign multiple Transceiver blocks the same Modbus Unit ID. Must range between 0 and 255.

According to the Modbus standard, unit ID 255 means NON-SIGNIFICANT. When addressing a Speedgoat Modbus Server and the unit identifier is set to 255 but unit 255 is not configured in the server itself, the requested command is performed on the first unit specified in the server configuration.

Function Code

Select the Modbus Function Code you want to use for your communication. The options are:

  • FC1 (Read Multiple Coils)

    The output will be an array of booleans.

  • FC2 (Read Multiple Discrete Inputs)

    The output will be an array of booleans.

  • FC3 (Read Multiple Holding Registers)

    The output will be an array of uint16.

  • FC4 (Read Multiple Input Registers)

    The output will be an array of uint16.

  • FC5 (Write Single Coil)

    The input will be a single uint16.

  • FC6 (Write Single Holding Register)

    The input will be a single uint16.

  • FC15 (Write Multiple Coils)

    The input will be an array of uint16.

  • FC16 (Write Multiple Holding Registers)

    The input will be an array of uint16.

Refer to the Modbus usage notes for further information about function codes.

Data Index

The first index of the data range you want to send or receive. Must range between 0 and 65535.

  • For Coils and Discrete Inputs, the parameter defines the start bit.

  • For Holding Registers and Input Registers, the value defines the start word.

Data Quantity

The length of the data range you want to send or receive. Index + Quantity must not exceed 65536.

Polling Interval

The polling interval is the time interval between sending Modbus requests to the server. Must range between 0 and 7,200,000 milliseconds, which corresponds to a maximum of 2 hours. The default value is 50 ms.

Manage Requests

Tick this checkbox if you want to control sending Modbus requests. This activates the ENA input port of the Transceiver block. If the sending is stopped, the Transceiver will still be able to receive data and update its output port.

Update on Change

Tick this checkbox if you want to send Modbus requests only when the data on the TX port has changed. This behavior is only available if function codes FC5, FC6, FC15 or FC16 are selected. Additionally, the Manage Requests functionality is disabled while using Update on Change. The Polling Interval is still used as a "minimal" sending interval. To send as fast as possible set the Polling Interval to 1 ms.

Sample Time

Defines the base sample time at which this driver block gets its sample hit. This parameter can also be set to -1 for inherited sample time. The units are in seconds.