IO756 - Setup
IO756 - Setup — Configure the IO756 IO
module
Library
Simulink Real-Time - Speedgoat

Description
Your model can contain only one Setup block
for each I/O module in your target machine.
Ports
This driver block has no input or output ports.
Parameters
Configuration-Tab
- Module ID
The Module ID has two functions:
It logically connects the Setup block and its I/O blocks
It also informs the auto-search feature of the PCI Slot parameter. If only
one I/O module of this family is installed, the Module ID must be set to
1. To see how each I/O module maps to a
Module ID, use this Speedgoat API:
speedgoat.getIoInterfaces("TargetName", "mySpeedgoat")
This Setup block belongs to two families of I/O modules that use the same hardware
for multiple protocols. Across both families, the Module ID must be unique.
IO64X/IO75X (single-node modules): IO641,
IO642, IO643, IO644, IO750, IO751, IO752, IO753, IO754, IO755, IO756,
IO758
IO64X-32/IO75X-32 (multi-node modules):
IO642-32, IO752-32, IO754-32, IO756-32
If the PCI Slot parameter is set to -1
(auto-search), the Module ID must be in the range 1:n, where 'n' cannot be larger
than the number of modules of this type installed in the target machine. Not all
installed I/O modules need to be used.
To use this Setup block with a multi-node I/O module (IO75X-32 family), the Module
ID must be defined as a two-element vector. The second vector element is the
sub-module ID. It describes the specific node (1:32) within the I/O module. The 32
nodes are internally connected to form two linear networks (daisy-chain), where the
first and the last node of both chains are externally accessible. If one node is not
configured (has no Setup block), the chain terminates at this point. The sub-module
IDs must therefore start at node 1, 16, 17 or 32 and not have any gaps.
![[Note]](images/note.png) | Note |
|---|
When using I/O modules of both families simultaneously (single-node and
multi-node I/O modules), always use explicit addressing in the PCI Slot parameter. Ignore the Module IDs returned by
the getIoInterfaces function and instead assign unique Module IDs accross all
modules used. |
-
Configuration Mode
![[Note]](images/note.png) | Note |
|---|
This parameter is obsolete and will be removed. Please always
select Warmstart. |
-
PCI Slot (-1: auto-search)
There are two approaches for mapping the block to a specific I/O
module installed in your target machine. All modules of the same
family (see Module ID above) must be configured using the same
method.
- Auto-Search: with the default value -1 the I/O module will be
automatically located in the target machine. If you have
multiple modules of the same family, the Module ID (first
vector element for a multi-node module) defines which module
is associated with this block. To see how each I/O module
maps to a Module ID, use this Speedgoat API:
speedgoat.getIoInterfaces("TargetName", "mySpeedgoat") - Explicit Addressing: to explicitly define the logical
address of the I/O module in the target machine, you can
provide the PCI bus and slot numbers as a vector: [bus,
slot]. To determine these numbers, run the following command
in the MATLAB command window:
speedgoat.getIoInterfaces("TargetName", "mySpeedgoat", "Advanced", true)Note
that the PCI address can change whenever an I/O module is
added or removed. Usually, auto-search is the best option.
Warmstart-Tab
-
Input Instance-ID
Instance-ID of the communication point for input data (Target to
Originator direction)
-
Input Data Length
Data length in byte should be in the range 0…504
-
RT transfer format (Input)
Available settings are: "Connection is pure data and modeless" or
"32-bit run/idle header" and should correspond to the settings of
Ethernet/IP Scanner.
-
Output Instance-ID
Instance-ID of the communication point for output data (Originator to
Target direction)
-
Output Data Length
Data length in byte should be in the range 0…504
-
RT Transfer Format (Output)
Available settings are: "Connection is pure data and modeless" or
"32-bit run/idle header" and should correspond to the settings of
Ethernet/IP Scanner.
-
Enable BOOTP
If enabled, the device tries to obtain its IP configuration from a
BOOTP server.
-
Enable DHCP
If enabled, the device tries to obtain its IP configuration from a
DHCP server.
-
IP Address
IP Address (if neither BOOTP nor DHCP is selected)
-
Network Mask
Network mask (if neither BOOTP nor DHCP is selected)
-
Gateway
Gateway Address (if neither BOOTP nor DHCP is selected)
Warmstart Device Info-Tab
-
Vendor ID
Vendor identification: This is an identification number for the
manufacturer of an EtherNet/IP device. The value 0 is not valid.
-
CIP Device Type (Product Type)
CIP Device Type. It is used to identify the device profile that a
particular product is using. Device profiles define minimum requirements
a device must implement as well as common options.
-
Product Code
The vendor assigned Product Code identifies a particular product
within a device type. Each vendor assigns this code to each of its
products.
-
Serial Number
This parameter is a number used in conjunction with the Vendor ID to
form a unique identifier for each device on any CIP network.
-
Minor Revision
Minor revision number of the simulated device
-
Major Revision
Major revision number of the simulated device
-
Device Name
This text string should represent a short description of the
product/product family represented by the product code.
The parameters Vendor ID, Product Type, Product Code, Minor revision and Major
revision can be used from Ethernet/IP Scanner for "electronic keying". If
"electronic keying" was configured for exact match, then all this parameters of the
adapter match with the configuration of the scanner. It is also possible, that
scanner checks some of this parameters before establishing the communication.